© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2011.
Unauthorized copying and distribution is a violation of law.
Order No: PHAAM1111087C1
Indoor Unit Outdoor Unit
CS-E9NKUAW
CS-E12NKUAW
CU-E9NKUA
CU-E12NKUA
Please file and use this manual together with the service manual for Model No. CU-2E18NBU, Order No. PHAAM1111120A1.
TABLE OF CONTENTS
1. Safety Precautions.............................................3
2. Specification .......................................................5
3. Features ..............................................................8
4. Location of Controls and Components ...........9
4.1 Indoor Unit....................................................9
4.2 Outdoor Unit.................................................9
4.3 Remote Control ............................................9
5. Dimensions.......................................................10
5.1 Indoor Unit..................................................10
5.2 Outdoor Unit...............................................11
6. Refrigeration Cycle Diagram...........................12
7. Block Diagram ..................................................13
8. Wiring Connection Diagram............................14
8.1 Indoor Unit..................................................14
8.2 Outdoor Unit ...............................................15
9. Electronic Circuit Diagram ..............................16
9.1 Indoor Unit..................................................16
9.2 Outdoor Unit ...............................................17
10. Printed Circuit Board .......................................18
10.1 Indoor Unit..................................................18
10.2 Outdoor Unit ...............................................20
11. Installation Instruction.....................................21
11.1 Select the Best Location ............................21
11.2 Indoor Unit..................................................22
11.3 Outdoor Unit ...............................................26
12. Operation Control.............................................29
12.1 Basic Function............................................29
12.2 Indoor Fan Motor Operation.......................30
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the products dealt with in this service information by anyone else could result in serious injury or death.
Przeglądanie stron 0
1 2 3 4 5 6 ... 89 90

Podsumowanie treści

Strona 1

© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2011. Unauthorized copying and distribution is a violation of law. Order No: PHAAM1111087C1 Indoor Un

Strona 2

10 5. Dimensions 5.1 Indoor Unit

Strona 4

12 6. Refrigeration Cycle Diagram

Strona 5 - 2. Specification

13 7. Block Diagram

Strona 6

14 8. Wiring Connection Diagram 8.1 Indoor Unit

Strona 7

15 8.2 Outdoor Unit

Strona 8 - 3. Features

16 9. Electronic Circuit Diagram 9.1 Indoor Unit

Strona 10 - 5. Dimensions

18 10. Printed Circuit Board 10.1 Indoor Unit 10.1.1 Main Printed Circuit Board

Strona 11 - 5.2 Outdoor Unit

19 10.1.2 Power Printed Circuit Board 10.1.3 Indicator Printed Circuit Board

Strona 12

2 12.3 Outdoor Fan Motor Operation ...31 12.4 Airflow Direction...31 12.5 Quiet Operation (

Strona 13 - 7. Block Diagram

20 10.2 Outdoor Unit 10.2.1 Main Printed Circuit Board

Strona 14 - 8. Wiring Connection Diagram

21 11. Installation Instruction 11.1 Select the Best Location 11.1.1 Indoor Unit  Do not install the unit in excessive oil fume area such as kitche

Strona 15 - 8.2 Outdoor Unit

22 11.2 Indoor Unit 11.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent if from the vibration. T

Strona 16 - 9.1 Indoor Unit

23 11.2.3 Indoor Unit Installation 11.2.3.1 For the right rear piping 11.2.3.2 For the right bottom piping 11.2.3.3 For the embedded piping

Strona 17 - 9.2 Outdoor Unit

24 11.2.4 Connect the Cable to the Indoor Unit 1. The inside and outside connection cable can be connected without removing the front grille. 2.

Strona 18 - 10. Printed Circuit Board

25 11.2.5 Wiring Stripping and connecting requirement 11.2.5.1 Cutting and flaring the piping 1 Please cut using pipe cutter and then remove the

Strona 19

26 11.3 Outdoor Unit 11.3.1 Install the Outdoor Unit  After selecting the best location, start installation according to indoor/outdoor unit instal

Strona 20 - 10.2 Outdoor Unit

27 11.3.2.3 Connecting the piping to outdoor multi Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare aft

Strona 21 - 11. Installation Instruction

28 8. Mount valve caps onto the 2-way valve and the 3-way valve. o Be sure to check for gas leakage. 11.3.3.1 Connect the Cable to the Outdoor U

Strona 22 - 11.2 Indoor Unit

29 12. Operation Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as

Strona 23

3 CAUTION WARNING WARNING 1. Safety Precautions  Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.  Electrical work

Strona 24

30 12.1.4.2 Automatic Operation  This mode can be set using remote control and the operation is decided by remote control setting temperature, remot

Strona 25

31 [Heating] o According to indoor pipe temperature, automatic heating fan speed is determined as follows.  Feedback control o Immediately after

Strona 26 - 11.3 Outdoor Unit

32 12.4.2 Horizontal Airflow The horizontal airflow direction louvers can be adjusted manually by hand. 12.5 Quiet Operation (Cooling Mode/Cooling

Strona 27 - 11.3.2.4 Gas Leak Checking

33  Control contents o Fan speed auto  Indoor FM RPM depends on pipe temperature sensor of indoor heat exchanger. Auto fan speed is changed from n

Strona 28 - 11.3.3.2 Piping Insulation

34 12.10 Indication Panel Note:  If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation

Strona 29 - 12. Operation Control

35 13. Operation Control (For Multi Split Connection) During multi split connection, indoor unit’s operation controls are same with single split conn

Strona 30 - 12.1.4.2 Automatic Operation

36 13.4 Automatic Operation  This mode can be set using remote control and the operation is decided by remote control setting temperature, remote co

Strona 31 - 12.4 Airflow Direction

37 14. Protection Control 14.1 Protection Control For All Operations 14.1.1 Restart Control (Time Delay Safety Control)  The compressor will

Strona 32 - 12.4.2 Horizontal Airflow

38 14.1.5 Compressor Overheating Prevention Control  Instructed frequency for compressor operation will be regulated by compressor discharge tem

Strona 33 - 12.9 Auto Restart Control

39 14.2.2 Cooling Overload Control  Pipe temperature limitation / restriction. o Detects the outdoor pipe temperature and carry out restrictio

Strona 34 - 12.10 Indication Panel

4 CAUTION 19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refriger

Strona 35 - 13.3 Heating Operation

40 14.2.6.2 Outdoor Air Temperature Control  The maximum current value is regulated when the outdoor air temperature rise above 57.2°F in order to

Strona 36 - 13.8 Indication Panel

41 15. Servicing Mode 15.1 Auto Off/On Button 1 AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button i

Strona 37 - 14. Protection Control

42 Press Auto OFF/ON button to toggle remote control receiving sound. - Short “beep”: Turn OFF remote control receiving sound. - Long “beep”: Turn O

Strona 38

43 16. Troubleshooting Guide 16.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems befor

Strona 39

44 16.1.1 Relationship between the condition of the air conditioner and pressure and electric current  Carry out the measurements of pressure, ele

Strona 40 - 14.2.6.6 Deice Operation

45 16.2 Breakdown Self Diagnosis Function 16.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code)  Once error occurred during operation, t

Strona 41 - 15. Servicing Mode

46 16.3 Error Code Table

Strona 42 - 15.2 Remote Control Button

47 Note: “○” – Frequency measured and fan speed fixed The memory data of error code is erased when the power supply is cut off, or press the Auto Sw

Strona 43 - 16. Troubleshooting Guide

48 16.4 Self-diagnosis Method 16.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions  During startup and operation of c

Strona 44

49 16.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions  During startup, error code appears when different types of

Strona 45 - 16.2.2 To Make a Diagnosis

5 2. Specification Indoor CS-E9NKUAW CS-E12NKUAW Model Outdoor CU-E9NKUA CU-E12NKUA Performance Test Condition ARI ARI Phase, Hz Single, 60 Sing

Strona 46 - 16.3 Error Code Table

50 16.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heati

Strona 47

51 16.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the

Strona 48 - 16.4 Self-diagnosis Method

52 16.4.5 H16 (Outdoor Current Transformer Open Circuit) Malfunction Decision Conditions  A current transformer (CT) is detected by checking the co

Strona 49

53 16.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during fan

Strona 50

54 16.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, th

Strona 51

55 16.4.8 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, th

Strona 52

56 16.4.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating,

Strona 53

57 16.4.10 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and h

Strona 54

58 16.4.11 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality) Malfunction Decision Conditions  During startup and operation of cooling a

Strona 55

59 16.4.12 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions  The supply power is detected for its requirement b

Strona 56

6 Type Propeller Propeller Material PP PP Motor Type DC (8 poles) DC (8 poles) Input Power W - - Output Power W 40 40 Outdoor Fan Spee

Strona 57

60 16.4.13 H36 (Outdoor Gas Pipe Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temp

Strona 58

61 16.4.14 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and he

Strona 59

62 16.4.15 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during f

Strona 60

63 16.4.16 H98 (Indoor High Pressure Protection) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Condit

Strona 61

64 16.4.17 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Malfunction Decision Conditions  Freeze prevention control takes place

Strona 62

65 16.4.18 F11 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  When cooling operation, when indoor pipe temperature

Strona 63

66 16.4.19 F17 (Indoor Standby Units Freezing Abnormality) Malfunction Decision Conditions  When the different between indoor intake air temperatur

Strona 64

67 16.4.20 F90 (Power Factor Correction Protection) Malfunction Decision Conditions  During startup and operation of cooling and heating, when Powe

Strona 65

68 16.4.21 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions  During cooling, compressor frequency = Fcmax.  During cooling

Strona 66

69 16.4.22 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor r

Strona 67

7 DRY BULB WET BULB DRY BULB WET BULB Maximum 89.6 73.4 89.6 73.4 Indoor Operation Range (Cooling) Minimum 60.8 51.8 60.8 51.8 Maximum 109.4 78.8

Strona 68

70 16.4.23 F95 (Cooling High Pressure Abnormality) Malfunction Decision Conditions During operation of cooling, when outdoor unit heat exchanger hi

Strona 69

71 16.4.24 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (212°F) is dete

Strona 70

72 16.4.25 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature d

Strona 71

73 16.4.26 F98 (Input Over Current Detection) Malfunction Decision Conditions During cooling and heating operation, when an input over-current (16.

Strona 72

74 16.4.27 F99 (Output Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an output over-current

Strona 73

75 WARNING 17. Disassembly and Assembly Instructions High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capa

Strona 74 - Abnormal resistance 0 or ∞

76 17.1.1.2 To remove discharge grille

Strona 75 - Removal Procedures

77 17.1.1.3 To remove control board 17.1.1.4 To remove cross flow fan and indoor fan motor

Strona 77

79 18. Technical Data 18.1 Operation Characteristics 18.1.1 CS-E9NK CU-E9NK  Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o

Strona 78

8 3. Features  Inverter Technology o Wider output power range o Energy saving o Quick Cooling o More precise temperature control  Environment

Strona 79 - 18. Technical Data

80  Piping Length Characteristic Cooling o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature

Strona 80

81  Heating Characteristic o Room temperature: 68°F (DBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Frequency

Strona 81

82  Piping Length Characteristic Heating o Room temperature: 68°F (DBT) o Operation condition: High fan speed o Outdoor temperature: 47°F (DBT

Strona 82

83 18.1.2 CS-E12NK CU-E12NK  Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping l

Strona 83 - 18.1.2 CS-E12NK CU-E12NK

84  Piping Length Characteristic Cooling o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature

Strona 84

85  Heating Characteristic o Room temperature: 68°F (DBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Frequency

Strona 85

86  Piping Length Characteristic Heating o Room temperature: 68°F (DBT) o Operation condition: High fan speed o Outdoor temperature: 47°F (DBT

Strona 86

87 19. Exploded View and Replacement Parts List 19.1 Indoor Unit Note The above exploded view is for the purpose of parts disassembly and replaceme

Strona 87 - 19.1 Indoor Unit

88 REF. NO. PART NAME & DESCRIPTION QTY. CS-E9NKUAW CS-E12NKUAW REMARK 1 CHASSIS COMPLETE 1 CWD50C1633 ← 2 FAN MOTOR 1 L6CBYYYL0055 ←

Strona 88

89 19.2 Outdoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as s

Strona 89 - 19.2 Outdoor Unit

9 4. Location of Controls and Components 4.1 Indoor Unit 4.2 Outdoor Unit 4.3 Remote Control

Strona 90

90 REF. NO. PART NAME & DESCRIPTION QTY. CU-E9NKUA CU-E12NKUA REMARK 1 CHASSIS ASSY 1 CWD50K2081A ← 2 FAN MOTOR BRACKET 1 CWD541089 ←