Split System Submittal Data
System: KE36NKU Indoor: CS-KE36NKU Outdoor: CU-36NKU
Wall Mounted Heat Pump
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 230/208/1/60
Circuit Ampacity (A) 16.5-18.0
Fuse Size, Max.(A) 45
Compressor DC Twin Rotary (Inverter)
No. Used 1
R.L. Amps - L.R. (A) 20.0-31.0
Outdoor Unit
Fan Type Propeller
Dia (in.) - No. Speeds 19-9/32” Auto (Hi, Me, Lo)
Type Drive Direct / DC Motor
No. Poles (RPM) 8-750
No. Motors (W) 1-142
F.L. Amps (A) 19.6-21.5
Coil Type Aluminum Fin and Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2-21.2
Rows - F.P.I. 2 - 18.1
Face Area (sq.ft.) 8.05
Tube Size (in.) 3/8”
Indoor Unit
Fan Type Cross Flow
Dia (in.) 3-15/16” x 32”
No. Speeds Auto and 3 steps
No. Poles (RPM (Cool / Heat), High) 8-1,370 / 1,450
No. Motors (W) 47
CFM (Hi/Med/Low) Cooling 630/530/412
CFM (Hi/Med/Low) Heating 671/559/441
Operating Sound-Hi/Me/Lo/ dB-A
(Cool)
49 / 44 / 39
Operating Sound-Hi/Me/Lo/ dB-A
(Heat)
49 / 44 / 39
F.L. Amps 0.4
Coil Type
Aluminum Plate Fin & Copper Tube
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2-19.5
Face Area (sq. ft.) 4.55
Tube Size (in.) 3/8”
Drain Connection Size (in.) 1-1/4”
Refrigerant R410A
Lbs. - R410a (outdoor unit) 6.5
Refrigerant Control Electronic Expansion Valve
Refrigerant Tubing Connections Flare
Line Length, Max (ft.) 165
Line Difference, Max (ft.) 50 (outdoor lower), 100 (outdoor
higher)
Line Size (in. O.D. Discharge) 3/8”
Line Size (in. O.D. Suction) 5/8”
Pre-charge, tubing length at
shipment
100’
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 12-7/32 x 44-7/8 x 14-31/32
Indoor Unit (Uncrated) (in.) 11-3/16 x 41-15/16 x 9-1/16
Outdoor Unit (Crated) (in.) 42-3/8 x 40 x 16-3/8
Outdoor Unit (Uncrated) (in.) 35-13/16 x 37-1/32 x 13-3/8
Weight (lbs.)
(Indoor) Net 32.0
(Indoor) Shipping 39.7
(Outdoor) Net 185.2
(Outdoor) Shipping 207.2
(Indoor) Shipping Volume (cu.ft.) 4.59
(Outdoor) Shipping Volume (cu.ft.) 15.88
Przeglądanie stron 0
1 2 3

Podsumowanie treści

Strona 1 - Split System Submittal Data

Split System Submittal DataSystem: KE36NKU Indoor: CS-KE36NKU Outdoor: CU-36NKUWall Mounted Heat PumpApproval:Date:Construction:Unit#:Drawing#:Job