11. Installation Instruction
11.1 Select the Best Location
11.1.1 Indoor Unit
Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit
shall be at least 8.2 ft.
11.1.2 Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Recommended installation height for outdoor unit
should be above the seasonal snow level.
Example: For E9NKUAW
If the unit is installed at 32.8 ft distance, the quantity
of additional refrigerant should be 1.64 oz ....
(32.8 - 24.6) ft x 0.2 oz/ft = 1.64 oz.
11.1.3 Indoor/Outdoor Unit Installation
Diagram
Przeglądanie stron 0
1 2 3 4 5 6 7 8

Podsumowanie treści

Strona 1 - 11. Installation Instruction

21 11. Installation Instruction 11.1 Select the Best Location 11.1.1 Indoor Unit  Do not install the unit in excessive oil fume area such as kitche

Strona 2 - 11.2 Indoor Unit

22 11.2 Indoor Unit 11.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent if from the vibration. T

Strona 3

23 11.2.3 Indoor Unit Installation 11.2.3.1 For the right rear piping 11.2.3.2 For the right bottom piping 11.2.3.3 For the embedded piping

Strona 4

24 11.2.4 Connect the Cable to the Indoor Unit 1. The inside and outside connection cable can be connected without removing the front grille. 2.

Strona 5

25 11.2.5 Wiring Stripping and connecting requirement 11.2.5.1 Cutting and flaring the piping 1 Please cut using pipe cutter and then remove the

Strona 6 - 11.3 Outdoor Unit

26 11.3 Outdoor Unit 11.3.1 Install the Outdoor Unit  After selecting the best location, start installation according to indoor/outdoor unit instal

Strona 7 - 11.3.2.4 Gas Leak Checking

27 11.3.2.3 Connecting the piping to outdoor multi Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare aft

Strona 8 - 11.3.3.2 Piping Insulation

28 8. Mount valve caps onto the 2-way valve and the 3-way valve. o Be sure to check for gas leakage. 11.3.3.1 Connect the Cable to the Outdoor U

Komentarze do niniejszej Instrukcji

Brak uwag