Panasonic E18NKUA Instrukcja Obsługi

Przeglądaj online lub pobierz Instrukcja Obsługi dla Klimatyzatory typu split Panasonic E18NKUA. Panasonic E18NKUA Service Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 0
© Panasonic Appliances Air-Conditioning (M) Sdn. Bhd. 2012.
Unauthorized copying and distribution is a violation of law.
Order No: PAPAMY1204088CE
Indoor Unit Outdoor Unit
CS-E18NKUA
CS-E24NKUA
CU-E18NKUA
CU-E24NKUA
TABLE OF CONTENTS
1. Safety Precautions.............................................3
2. Specification .......................................................5
3. Features ..............................................................8
4. Location of Controls and Components ...........9
4.1 Indoor Unit....................................................9
4.2 Outdoor Unit.................................................9
4.3 Remote Control ............................................9
5. Dimensions.......................................................10
5.1 Indoor Unit..................................................10
5.2 Outdoor Unit...............................................11
6. Refrigeration Cycle Diagram...........................12
7. Block Diagram ..................................................13
8. Wiring Connection Diagram............................14
8.1 Indoor Unit..................................................14
8.2 Outdoor Unit ...............................................15
9. Electronic Circuit Diagram ..............................16
9.1 Indoor Unit..................................................16
9.2 Outdoor Unit ...............................................17
10. Printed Circuit Board .......................................18
10.1 Indoor Unit..................................................18
10.2 Outdoor Unit ...............................................20
11. Installation Instruction.....................................22
11.1 Select the Best Location ............................22
11.2 Indoor/Outdoor Unit Installation Diagram...22
11.3 Indoor Unit..................................................23
11.4 Outdoor Unit ...............................................27
12. Operation Control.............................................30
12.1 Basic Function............................................30
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the products dealt with in this service information by anyone else could result in serious injury or death.
Przeglądanie stron 0
1 2 3 4 5 6 ... 81 82

Podsumowanie treści

Strona 1

© Panasonic Appliances Air-Conditioning (M) Sdn. Bhd. 2012. Unauthorized copying and distribution is a violation of law. Order No: PAPAMY1204088CE

Strona 2

10 5. Dimensions 5.1 Indoor Unit

Strona 4

12 6. Refrigeration Cycle Diagram

Strona 5 - 2. Specification

13 7. Block Diagram

Strona 6

14 8. Wiring Connection Diagram 8.1 Indoor Unit

Strona 7

15 8.2 Outdoor Unit

Strona 8 - 3. Features

16 9. Electronic Circuit Diagram 9.1 Indoor Unit

Strona 10 - 5. Dimensions

18 10. Printed Circuit Board 10.1 Indoor Unit 10.1.1 Main Printed Circuit Board

Strona 11 - 5.2 Outdoor Unit

19 10.1.2 Power Printed Circuit Board 10.1.3 Indicator and Receiver Printed Circuit Board

Strona 12

2 12.2 Indoor Fan Motor Operation ...31 12.3 Outdoor Fan Motor Operation ...32 12.4 Airflow Direction...

Strona 13 - 7. Block Diagram

20 10.2 Outdoor Unit 10.2.1 Main Printed Circuit Board

Strona 14 - 8. Wiring Connection Diagram

21 10.2.2 Noise Filter Printed Circuit Board

Strona 15 - 8.2 Outdoor Unit

22 11. Installation Instruction 11.1 Select the Best Location 11.1.1 Indoor Unit  Do not install the unit in excessive oil fume area such as kitche

Strona 16 - 9.1 Indoor Unit

23 11.3 Indoor Unit 11.3.1 How to Fix Installation Plate The mounting wall must be strong and solid enough to prevent it from the vibration. The c

Strona 17 - 9.2 Outdoor Unit

24 11.3.3 Indoor Unit Installation 11.3.4 For the right rear piping 11.3.5 For the right bottom piping 11.3.6 For the embedded piping

Strona 18 - 10. Printed Circuit Board

25 11.3.7 Connect the Cable to the Indoor Unit 1. The inside and outside connecting cable can be connected without removing the front grille. 2.

Strona 19

26 11.3.8 Wiring Stripping and connecting requirement 11.3.9 Cutting and flaring the piping 1 Please cut using pipe cutter and then remove the b

Strona 20 - 10.2 Outdoor Unit

27 11.4 Outdoor Unit 11.4.1 Install the Outdoor Unit  After selecting the best location, start installation according to indoor/outdoor unit instal

Strona 21

28 11.4.3 Evacuation of the equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the followi

Strona 22 - 11. Installation Instruction

29 9. Secure the wire onto the control board with the holder (clamper). 10. After completing wiring connections, reattach the particular plate con

Strona 23 - 11.3 Indoor Unit

3 CAUTION WARNING WARNING 1. Safety Precautions  Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.  Electrical work

Strona 24

30 12. Operation Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as

Strona 25

31 12.1.5 Automatic Operation  This mode can be set using remote control and the operation is decided by remote control setting temperature, remote

Strona 26

32 [Heating] o According to indoor pipe temperature, automatic heating fan speed is determined as follows.  Feedback control o Immediately after

Strona 27 - 11.4 Outdoor Unit

33  Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions of the vane are

Strona 28

34  During quiet operation, if ON timer activates, quiet operation maintains.  After off, when on back, quiet operation is not memorised.  Contr

Strona 29 - 11.4.5 Piping Insulation

35 12.8 Timer Control 12.8.1 ON Timer Control  ON Timer can be set using remote control, where the unit with timer set will start operation earlier

Strona 30 - 12. Operation Control

36 13. Protection Control 13.1 Protection Control For All Operations 13.1.1 Restart Control (Time Delay Safety Control)  The compressor will not

Strona 31 - 12.1.5 Automatic Operation

37 13.1.5 Compressor Overheating Prevention Control  Instructed frequency for compressor operation will be regulated by compressor discharge tempera

Strona 32 - 12.4 Airflow Direction

38 13.2.2 Cooling Overload Control  Pipe temperature limitation / restriction. o Detects the outdoor pipe temperature and carry out restriction

Strona 33 - 12.4.2 Horizontal Airflow

39 13.2.6.3 Overload Protection Control  The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as show

Strona 34

4 CAUTION 19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refriger

Strona 35 - 12.10 Indication Panel

40 14. Servicing Mode 14.1 Auto Off/On Button 1 AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button i

Strona 36 - 13. Protection Control

41 Press Auto OFF/ON button to toggle remote control receiving sound. - Short “beep”: Turn OFF remote control receiving sound. - Long “beep”: Turn O

Strona 37 - E18NKUA, E24NKUA

42 15. Troubleshooting Guide 15.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems befor

Strona 38

43 15.1.1 Relationship between the condition of the air conditioner and pressure and electric current  Carry out the measurements of pressure, ele

Strona 39 - 13.2.6.6 Deice Operation

44 15.2 Breakdown Self Diagnosis Function 15.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code)  Once error occurred during operation, t

Strona 40 - 14. Servicing Mode

45 15.3 Error Code Table

Strona 41 - 14.2 Remote Control Button

46 Note: “○” – Frequency measured and fan speed fixed The memory data of error code is erased when the power supply is cut off, or press the Auto Sw

Strona 42 - 15. Troubleshooting Guide

47 15.4 Self-diagnosis Method 15.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions  During startup and operation of c

Strona 43

48 15.4.2 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heati

Strona 44 - 15.2.2 To Make a Diagnosis

49 15.4.3 H16 (Outdoor Current Transformer Open Circuit) Malfunction Decision Conditions  A current transformer (CT) is detected by checking the co

Strona 45 - 15.3 Error Code Table

5 2. Specification Indoor CS-E18NKUA CS-E24NKUA Model Outdoor CU-E18NKUA CU-E24NKUA Performance Test Condition ARI ARI Phase, Hz Single, 60 Sing

Strona 46

50 15.4.4 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during fan

Strona 47 - 15.4 Self-diagnosis Method

51 15.4.5 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, th

Strona 48

52 15.4.6 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, th

Strona 49

53 15.4.7 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating,

Strona 50

54 15.4.8 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and he

Strona 51

55 15.4.9 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions  The supply power is detected for its requirement by

Strona 52

56 15.4.10 H98 (Indoor High Pressure Protection) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Condit

Strona 53

57 15.4.11 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Malfunction Decision Conditions  Freeze prevention control takes place

Strona 54

58 15.4.12 F11 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  When cooling operation, when indoor pipe temperature

Strona 55

59 15.4.13 F90 (Power Factor Correction Protection) Malfunction Decision Conditions  During startup and operation of cooling and heating, when Powe

Strona 56

6 Type Propeller Propeller Material PP PP Motor Type DC Motor (8 poles) DC Motor (8 poles) Input Power W - - Output Power W 60 60 Outd

Strona 57

60 15.4.14 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions  During cooling, compressor frequency = Fcmax.  During cooling

Strona 58

61 15.4.15 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor r

Strona 59

62 15.4.16 F95 (Cooling High Pressure Abnormality) Malfunction Decision Conditions During operation of cooling, when outdoor unit heat exchanger hi

Strona 60

63 15.4.17 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (212.0°F) is de

Strona 61

64 15.4.18 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature d

Strona 62

65 15.4.19 F98 (Input Over Current Detection) Malfunction Decision Conditions During cooling and heating operation, when an input over-current (16.

Strona 63

66 15.4.20 F99 (Output Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an output over-current

Strona 64

67 WARNING 16. Disassembly and Assembly Instructions High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capa

Strona 65

68 16.1.1.2 To remove discharge grille

Strona 66 - Abnormal resistance 0 or ∞

69 16.1.1.3 To remove control board 16.1.1.4 To remove cross flow fan and indoor fan motor

Strona 67 - Removal Procedures

7 DRY BULB WET BULB DRY BULB WET BULB Maximum 89.6 73.4 89.6 73.4 Indoor Operation Range (Cooling) Minimum 60.8 51.8 60.8 51.8 Maximum 109.4 78.8

Strona 69

71 17. Technical Data 17.1 Operation Characteristics 17.1.1 CS-E18NK CU-E18NK  Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT)

Strona 70

72  Piping Length Characteristic Cooling o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature

Strona 71 - 17. Technical Data

73  Heating Characteristic o Room temperature: 68°F (DBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Frequency

Strona 72

74  Piping Length Characteristic Heating o Room temperature: 68°F (DBT) o Operation condition: High fan speed o Outdoor temperature: 47°F (DBT

Strona 73

75 17.1.2 CS-E24NK CU-E24NK  Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping l

Strona 74

76  Piping Length Characteristic Cooling o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature

Strona 75 - 17.1.2 CS-E24NK CU-E24NK

77  Heating Characteristic o Room temperature: 68°F (DBT) o Operation condition: High fan speed o Piping length: 24.6ft o Compressor Frequency

Strona 76

78  Piping Length Characteristic Heating o Room temperature: 68°F (DBT) o Operation condition: High fan speed o Outdoor temperature: 47°F (DBT

Strona 77

79 18. Exploded View and Replacement Parts List 18.1 Indoor Unit Note The above exploded view is for the purpose of parts disassembly and replacem

Strona 78

8 3. Features  Inverter Technology o Wider output power range o Energy saving o Quick Cooling o More precise temperature control  Environment

Strona 79 - 18.1 Indoor Unit

80 REF. NO. PART NAME & DESCRIPTION QTY. CS-E18NKUA CS-E24NKUA REMARK 1 CHASSIS COMPLETE 1 CWD50C1637 ← 2 FAN MOTOR 1 ARW7663AC ← O 3

Strona 80

81 18.2 Outdoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as s

Strona 81 - 18.2 Outdoor Unit

82 REF. NO. PART NAME & DESCRIPTION QTY. CU-E18NKUA CU-E24NKUA REMARK 1 CHASSIS ASS’Y 1 CWD52K1228A ← 2 ANTI-VIBRATION BUSHING 3 CWH50

Strona 82

9 4. Location of Controls and Components 4.1 Indoor Unit 4.2 Outdoor Unit 4.3 Remote Control