34
IEER = (0.02 * A) + (0.617 * B) + (0.238 * C) + (0.125 * D)
Where as:
A = EER at 100% net capacity at AHRI standard condition (95 deg F)
B = EER at 75% net capacity and reduced ambient (81.5 deg F)
C = EER at 50% net capacity and reduced ambient (68 deg F)
D = EER at 25% net capacity and reduced ambient (65 deg F)
Example:
A = 11.0 EER B = 16.0 EER C = 19.0 EER D = 23.0 EER
IEER = (0.02 * 11) + (0.617 * 16) + (0.238 * 19) + (0.125 * 23)
IEER = 0.2 + 9.8 + 4.5 + 2.9 =17.4 IEER
Part load performance of commercial HVAC systems
was represented as Integrated Part Load Performance
(IPLV) which was used until january 1, 2010. Then
a new methodology was adopted and defined as
Integrated Energy Efficiency Ratio (IEER).
IEER is intended to be used as a representation of part load performance
for energy comparisons of similar systems. For Variable Refrigerant
Flow (VRF) Multi Split systems AHRI Standard 1230 defines the process
to calculate IEER. In a most simplistic form IEER is calculated by
operating the system at 4 different capacities and applying a formula.
The basic calculation is as follows:
Some points to recognize from this calculation:
1. Full load EER (100% capacity) represents only 2% of
the overall IEER rating because the system would rarely
operate at this condition.
2. As overall capacity is reduced the system EER
increases significantly.
3. An ECOi system operating at 50% part load could
result in an efficiency increase of more than 70% over
the rated full load EER value.
4. Your actual efficiency could exceed the IEER rating
depending upon equipment sizing, environment and use
of the system.
Rating Standard: AHRI 1230
COOLING PERFORMANCE HEATING PERFORMANCE
SIMULTANEOUS
OPERATION
PERFORMANCE
System Model Number
Indoor Unit Rating
Type
Capacity
(Btuh)
EER IEER
High Heating 47F Low Heating 17F
Type
Capacity
(Btuh)
COP
Capacity
(Btuh)
COP
Simultaneous
Cooling-Heating
Efficiency (SCHE)
Heat Pump Normal U-72ME1U9 Ducted 72,000 11. 5 16.7 81,000 3.53 47,000 2.31
Heat Pump Normal U-72ME1U9 Mixed 70,500 11. 3 1 7. 1 79,000 3.42 44,500 2.28
Heat Pump Normal U-72ME1U9 Non-Ducted 69,500 11 1 7. 4 77,500 3.31 42,000 2.25
Heat Pump Salt Protect U-72ME1U9E Ducted 72,000 11. 5 16.7 81,000 3.53 47,000 2.31
Heat Pump Salt Protect U-72ME1U9E Mixed 70,500 11. 3 1 7. 1 79,000 3.42 44,500 2.28
Heat Pump Salt Protect U-72ME1U9E Non-Ducted 69,500 11 1 7. 4 77,500 3.31 42,000 2.25
Heat Pump Normal U-96ME1U9 Ducted 95,000 11. 1 16.3 106,500 3.32 69,000 2.26
Heat Pump Normal U-96ME1U9 Mixed 94,000 11. 1 16.7 104,500 3.32 63,500 2.26
Heat Pump Normal U-96ME1U9 Non-Ducted 93,000 11 17 103,000 3.31 58,500 2.25
Heat Pump Salt Protect U-96ME1U9E Ducted 95,000 11. 1 16.3 106,500 3.32 69,000 2.26
Heat Pump Salt Protect U-96ME1U9E Mixed 94,000 11. 1 16.7 104,500 3.32 63,500 2.26
Heat Pump Salt Protect U-96ME1U9E Non-Ducted 93,000 11 17 103,000 3.31 58,500 2.25
Heat Pump Normal WU-144ME1U9 Ducted 139,000 10.9 16.7 157,000 3.24 93,500 2.05
Heat Pump Normal WU-144ME1U9 Mixed 138,000 11 1 7. 1 154,000 3.28 88,500 2.15
Heat Pump Normal WU-144ME1U9 Non-Ducted 137,000 11 1 7. 4 151,000 3.31 83,500 2.25
Heat Pump Salt Protect WU-144ME1U9E Ducted 139,000 10.9 16.7 157,000 3.24 93,500 2.05
Heat Pump Salt Protect WU-144ME1U9E Mixed 138,000 11 1 7. 1 154,000 3.28 88,500 2.15
Heat Pump Salt Protect WU-144ME1U9E Non-Ducted 137,000 11 1 7. 4 151,000 3.31 83,500 2.25
Heat Pump Normal WU-168ME1U9 Ducted 164,000 10.8 16.4 184,000 3.22 114,000 2.05
Heat Pump Normal WU-168ME1U9 Mixed 162,000 10.7 16.8 181,000 3.22 106,000 2.05
Heat Pump Normal WU-168ME1U9 Non-Ducted 160,000 10.6 1 7. 2 178,500 3.21 98,000 2.05
Heat Pump Salt Protect WU-168ME1U9E Ducted 164,000 10.8 16.4 184,000 3.22 114,000 2.05
Heat Pump Salt Protect WU-168ME1U9E Mixed 162,000 10.7 16.8 181,000 3.22 106,000 2.05
Heat Pump Salt Protect WU-168ME1U9E Non-Ducted 160,000 10.6 1 7. 2 178,500 3.21 98,000 2.05
Heat Pump Normal WU-192ME1U9 Ducted 192,000 10.7 16.3 213,000 3.22 132,000 2.05
Heat Pump Normal WU-192ME1U9 Mixed 189,000 10.7 16.7 209,500 3.22 123,000 2.05
Heat Pump Normal WU-192ME1U9 Non-Ducted 186,000 10.6 17 206,000 3.21 114,000 2.05
Heat Pump Salt Protect WU-192ME1U9E Ducted 192,000 10.7 16.3 213,000 3.22 132,000 2.05
Heat Pump Salt Protect WU-192ME1U9E Mixed 189,000 10.7 16.7 209,500 3.22 123,000 2.05
Heat Pump Salt Protect WU-192ME1U9E Non-Ducted 186,000 10.6 17 206,000 3.21 114,000 2.05
Heat Pump Normal WU-216ME1U9 Ducted 203,000 10.7 16.3 228,000 3.22 136,000 2.05
Heat Pump Normal WU-216ME1U9 Mixed 200,500 10.7 16.6 224,500 3.22 128,000 2.05
Heat Pump Normal WU-216ME1U9 Non-Ducted 198,000 10.6 16.9 221,000 3.21 120,000 2.05
Heat Pump Salt Protect WU-216ME1U9E Ducted 203,000 10.7 16.3 228,000 3.22 136,000 2.05
Heat Pump Salt Protect WU-21
6ME1U9E Mixed 200,500 10.7 16.6 224,500 3.22 128,000 2.05
Heat Pump Salt Protect WU-216ME1U9E Non-Ducted 198,000 10.6 16.9 221,000 3.21 120,000 2.05
Heat Pump Normal WU-240ME1U9 Ducted 230,000 10.6 16.3 265,000 3.22 159,000 2.05
Heat Pump Normal WU-240ME1U9 Mixed 225,500 10.6 16.5 255,500 3.22 147,500 2.05
Heat Pump Normal WU-240ME1U9 Non-Ducted 221,000 10.6 16.7 246,000 3.21 136,000 2.05
IEER
INTEGRATED ENERGY EFFICIENCY RATIO
ECOi
TM
System Certified Efficiency Ratings