Wire type and length
Wiring run
Wire type
*
1
Diameter Max. length
Connected device
(
example: lobby
station or distributor)
«
Main monitor
ø 0.65 mm (22 AWG) approx. 100 m
ø 1.2 mm (17 AWG) approx. 200 m
Main monitor
«
Door bell
*
2
ø 0.5 mm - ø 1.2 mm
(
24 AWG - 17 AWG)
According to
specification of
connected device.
Main monitor
«
Connection device for
o
ption output (A
contact)
*3
ø 0.5 mm - ø 1.2 mm
(
24 AWG - 17 AWG)
According to
specification of
connected device.
Note the following when selecting wiring
*
1 Use 2-conductor (solid copper) wiring with a PE (polyethylene)-insulated PVC jacket.
Mid-capacitance, non-shielded cable is recommended.
R A certified power supply wiring has to be used with this equipment. The relevant national
installation and/or equipment regulations shall be considered. A certified power supply wiring not
lighter than ordinary polyvinyl chloride flexible wiring according to IEC 60227 shall be used.
*2 When using a door bell, select a device that meets the following guidelines:
R Connection device for option input terminal (IN1/IN2):
– Input method: No-voltage contact
– Open-circuit voltage between terminals: DC 10 V to 22 V
– Detection definite time: 0.1 second or more
– Resistance value: make: 500 W or less, break: 150 kW or more
*3 When using a connection device for option output (A contact), select a device that meets the
following guidelines:
R Connection device for option output (A contact) terminal (OUT1/OUT2):
– N/O dry closure contact
– 12 V AC/DC, less than 1 A