3-6-2. Installing the Ceiling Panel
After completing the wiring process, install the supplied
wiring cover before installing the panel.
It is not possible to install the wiring cover after installing
the panel.
The power must be turned ON in order to change the fl ap
angle. (Do not attempt to move the fl ap by hand. Doing so
may damage the fl ap.)
(1) Insert the temporary fasteners (stainless steel) on the
inside of the ceiling panel into the square holes on the
unit to temporarily fasten the ceiling panel in place.
(Fig. 3-20-1)
The ceiling panel must be installed in the correct
●
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the ceiling panel corner with the
correct positions on the unit.
To remove the ceiling panel, support the ceiling panel
●
while pressing the temporary fasteners toward the
outside. (Fig. 3-20-1)
(2) Align the panel installation holes and the unit screw
holes.
(3) Tighten the supplied washer head screws at the 4
panel installation locations so that the panel is
attached tightly to the unit. (Fig. 3-20-2)
(4) Check that the panel is attached tightly to the ceiling.
At this time, make sure that there are no gaps between
●
the unit and the ceiling panel, or between the ceiling
panel and the ceiling surface. (Fig. 3-21)
If there is a gap between the panel and the ceiling,
●
leave the ceiling panel attached and make fi ne
adjustments to the installation height of the unit to
eliminate the gap with the ceiling. (Fig. 3-21)
If the screws are not suffi ciently
●
tightened, trouble such as that shown
in the fi gure below may occur. Be sure
to tighten the screws securely.
If a gap remains between the ceiling
●
surface and the ceiling panel even
after the screws are tightened, adjust
the height of the unit again.
The height of the unit can be adjusted from the
ceiling panel corner hole, with the ceiling panel
attached, to an extent that does not affect the
unit levelness, the drain hose, or other elements.
Square hole in unit
Temporary
fastener
Push when
you remove
Temporary
fastener
Fig. 3-20-1
Drain tubing corner
Refrigerant tubing
corner
DRAIN mark
Panel installation hole
(4 locations)
REF. PIPE
mark
Washer head
screws
Ceiling panel
After completing the
wiring process, install
the supplied wiring cover
before installing the panel.
It is not possible to install
the wiring cover after
installing the panel.
Fig. 3-20-2
Do not allow
gaps
Ceiling panel
Main unit
Ceiling surface
Fig. 3-21
Insert a wrench
or other tool into
the corner cover
installation hole
and make fine
adjustments to
the unit nut.
Fig. 3-22
Air leakage
Air leakage from
ceiling surface
Staining
Condensation, water leakage
Adjust so that there are no gaps.
Fig. 3-23
Fig. 3-19-1
Screw (supplied)
M4-8 or 5/32" – 5/16"
Wiring cover (supplied) Power supply outlet
Inter-unit control wiring
Fig. 3-19-2