3-30. Installing the Duct
Connect the duct supplied in the fi eld.
Air inlet side
Attach the duct and intake-side fl ange (fi eld supply).
Connect the fl ange to the main unit with 10 -
Ø
1/8" (Hole) screws.
Wrap the intake-side fl ange and duct connection area with aluminum tape or something similar to prevent air
escaping.
CAUTION
When attaching a duct to the intake-side, be sure to attach an air fi lter inside the air passage on the intake-side.
(Use an air fi lter whose dust collecting effi ciency is at least 50% in a gravimetric technique.)
The included fi lter is not used when the intake duct is attached.
Air outlet side
Connect the duct according to the air outside of the outlet-side fl ange.
Wrap the outlet-side fl ange and the duct connection area with aluminum tape or something similar to prevent air
escaping.
CAUTION
Be sure to insulate the duct to prevent condensation from forming.
(Material: glass wool or polyethylene foam, 1 in. thick)
Use electric insulation between the duct and the wall when using metal ducts to pass metal laths of the net or fence
shape or metal plating into wooden buildings.
Be sure to explain about the way of maintaining and cleaning local procurements (air fi lter, grille [both air outlet and
suction grille], etc.) to your customer.
Flange
(Field supply)
Connection screw (×10)
Rectangular solid duct
(Field supply)
Flange
Insulation material
(Field supply)
Air inlet side
Air outlet side
Main unit
Fig. 3-106