(5) Before suspending the indoor unit, remove the 2 or 3 screws on the
latch of the air-intake grilles, open the grilles, and remove them by
pushing the claws of the hinges as shown in Fig. 3-135. Then remove
both side panels sliding them along the unit toward the front after
removing the 2 attachment screws. (Fig. 3-136)
(6) Carry out the preparation for suspending the indoor unit. The
suspension method varies depending on whether there is a suspended
ceiling or not. (Figs. 3-137 and 3-138)
(7) Suspend the indoor unit as follows:
a) Mount 1 washer and 2 hexagonal nuts on each suspension bolt as
shown in Fig. 3-139.
b) Lift the indoor unit, and place it on the washers through the notches,
in order to fi x it in place. (Fig. 3-140)
c) Tighten the 2 hexagonal nuts on each suspension bolt to suspend the
indoor unit as shown in Fig. 3-141.
NOTE
The ceiling surface is not always level. Please confi rm that the indoor unit is
evenly suspended. For the installation to be correct, leave a clearance of
about 3/8" between the ceiling panel and the ceiling surface and fi ll the gap
with an appropriate insulation or fi ller material.
(8) If the tubing and wiring are to go towards the rear of the unit, make
holes in the wall. (Fig. 3-142)
(9) Measure the thickness of the wall from the inside to the outside and cut
PVC pipe at a slight angle to fi t. Insert the PVC pipe in the wall.
(Fig. 3-143)
Slide toward
front side
Side panel
Fig. 3-136
Unit
Suspension bolt
(field supply)
Ceiling surface
Washer (supplied)
Double nut
(field supply)
Fixture
Fig. 3-137
Unit
Suspension bolt
(field supply)
Washer (supplied)
Washer (field supply)
Double nut
(field supply)
Fig. 3-138
Ceiling
surface
Approx.
63/64
"
Suspension bolt
Washer
(supplied)
Nut
(field supply)
Fig. 3-139
Fig. 3-141
Fig. 3-140
NOTE
The hole should be made at a slight downward slant to
the outside.
Indoor
side
Outdoor
side
Fig. 3-142
Cut at slight angle
PVC pipe (locally purchased)
INSIDE
W all
Slight
angle
PVC pipe
OUTSIDE
Fig. 3-143
VRF_Indoor_US.indb 46VRF_Indoor_US.indb 46 2011/09/30 12:23:092011/09/30 12:23:09