5-3. Insulating the Refrigerant Tubing
Tubing Insulation
Thermal insulation must be applied to all unit tubing,
including the distribution joint (purchased separately).
(Fig. 5-7)
* For gas tubing, the insulation material must be heat
resistant to 248°F or above. For other tubing, it must
be heat resistant to 176°F or above.
Insulation material thickness must be 25/64 in. or
greater.
If the conditions inside the ceiling exceed DB 86°F and
RH 70%, increase the thickness of the gas tubing
insulation material by 1 step.
CAUTION
If the exterior of the outdoor
unit valves has been fi nished
with a square duct covering,
make sure you allow
suffi cient space to use the
valves and to allow the
panels to be attached and
removed.
Taping the fl are nuts
Wind the white insulation tape around the fl are nuts at the
gas tube connections. Then cover up the tubing
connections with the fl are insulator, and fi ll the gap at the
union with the supplied black insulation tape. Finally,
fasten the insulator at both ends with the supplied vinyl
clamps. (Fig. 5-8)
Insulation material
The material used for insulation must have good
insulation characteristics, be easy to use, be age
resistant, and must not easily absorb moisture. (Fig. 5-9)
CAUTION
After a tube has been
insulated, never try to bend
it into a narrow curve
because it can cause the
tube to break or crack.
Two tubes arranged together
Liquid tubing
Gas tubing
Insulation
Three tubes arranged together
Liquid tubing
Gas tubing
Insulation
Cosmetic
(fi nishing) tape
Balance tubing
Three tubes arranged together
Suction tubing
Discharge tubing
Cosmetic
(fi nishing) tape
Balance tubing
Liquid tubing
Insulation
Fig. 5-7
Sealer (supplied)
Insulation tape (white)
(supplied)
Flare insulator (supplied)
Unit side
insulator
Flare nut
Vinyl clamps (supplied)
Tube insulator
(not supplied)
Heat resistant
248°F or above
Fig. 5-8
Refrigerant tubing and insulator
(not supplied)
Drain pipe and insulator
(not supplied)
Insulation
tape
Flare
insulator
Seal
The procedure used for
installing the insulator
for both gas and liquid
tubes are the same.
Drain insulator
and clamp.
Large
(supplied)
Vinyl
clamp
Packing
clamp.
Small
hose
band
(supplied)
Fig. 5-9
Never grasp the drain or refrigerant connecting outlets
when moving the unit.